Product Description  Core Identification: 1 Core: Brown 2 Cores: Brown, Blue 3 Cores: Brown, Black, Grey 4 Cores: Blue, Brown, Black, Grey; 5 Cores: Green/Yellow, Blue, Brown, Black, Grey Alternative core identification: White Cores with Black numbers Our FactoryÂ
Nominal Cross Section
Diameter of Conductor (Approx.)
Nominal Insulation Thickness
Nominal Sheath Thickness
Overall Diameter (Approx.)
mm^2
mm
mm
mm
mm
3x1.5
1.4
0.7
1.8
9.6
3x2.5
1.8
0.7
1.8
10.5
3x4
2.3
0.7
1.8
11.6
3x6
2.8
0.7
1.8
12.6
3x10
3.6
0.7
1.8
14.4
3x16
4.5
0.7
1.8
16.3
3x25
5.6
0.9
1.8
19.5
3x35
6.7
0.9
1.8
21.9
3x50
8.0
1
1.8
25.1
3x70
9.4
1.1
1.9
28.7
3x95
11.0
1.1
2.0
32.4
3x120
12.4
1.2
2.1
36.1
3x150
13.8
1.4
2.3
40.3
3x185
15.3
1.6
2.4
44.6
3x240
17.5
1.7
2.6
50.2
3x300
19.5
1.8
2.7
55.2
3x400
22.6
2
3.0
63.3
Applications
These cables are used for electricity supply in low voltage installation system, They are suitable for installation in indoors and outdoors, in cable ducts, under ground, in power and switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage.Construction
Conductors
The conductors shall be either of Class 1 or Class 2 of plain or metal-coated annealed copper or of plain aluminium or aluminium alloy, or of Class 5 of plain or metal-coated copper in accordance with IEC 60228.Insulation
XLPE material and thickness shall be as per IEC 60502 or BS 5467 rated for 90C continuous operation.Colour Code
Colour Code (1)
1 Core
Red or Black
2 Cores
Red, Black
3 Cores
Red, Yellow, Blue
4 Cores
Red, Yellow, Blue, Black
5 Cores
Red, Yellow, Blue, Black, Green
Above 5 Cores
Black Cores with White numerals
Colour Code (2)
1 Core
Brown or Blue
2 Cores
Brown, Blue
3 Cores
Brown, Black, Grey
4 Cores
Blue, Brown, Black, Grey
5 Cores
Green/Yellow, Blue, Brown, Black, Grey
Above 5 Cores
Black Cores with White numerals
Â
Assembly / Inner Covering
The inner coverings may be extruded or lapped. For cables with circular cores, except cables with more than five cores, a lapped inner covering shall be permitted only if the interstices between the cores are substantially filled. A suitable binder is permitted before application of an extruded inner covering. The material is compatible with the insulating material,The materials used for inner coverings and fillers shall be suitable for the operating temperature of the cable and compatible with the insulating material.For halogen free cables, the inner covering and fillers shall also be halogen free compound.Â
Armour
Aluminum/galvanized steel/steel wires applied helically over the Inner Covering as per IEC 60502-1, or double aluminum/steel tapes and copper/tinned copper wire can also be manufactured upon request.
 Outer Sheath
Outer sheath shall be of extruded PVC Type ST1/ST2 as per IEC 60502-1, Polyethylene type ST3/ST7, Halogen free compound ST8, Polychloroprene, chlorosulfonated polyethylene or similar polymers, type SE1 are also available on request.Fire Performance of Cable Sheaths
Cables can be supplied with special flame retardant PVC outer sheath to comply with the flame test requirements of IEC 60332-3-22, IEC 60332-3-23 and IEC 60332-3-24, Halogen Free material comply to IEC60754-1/2 and IEC 60684-2.
Â
Packing
Our Certificate
CONTACT US
Copper Conductor PVC Insulted PE Sheathed Electrical Cable
Wire Core Material: Bare Copper Wire
Certification: ISO, CCC, CE, RoHS
Brand: Luxing Cables
Normal Sectional Area: 1.5-800mm2
Standard: IEC, BS, VDE, GB/T
Trademark: CHANG QING TENG
Transport Package: Wooden Drum, Steel Wooden Drum, Steel Iron Drum
Specification: 0.6/1kv
Origin: Dezhou, Shandong
HS Code: 8544492100
Wire Core Material: Bare Copper Wire
Certification: ISO, CCC, CE, RoHS
Brand: Luxing Cables
Normal Sectional Area: 1.5-800mm2
Standard: IEC, BS, VDE, GB/T
Trademark: CHANG QING TENG
Transport Package: Wooden Drum, Steel Wooden Drum, Steel Iron Drum
Specification: 0.6/1kv
Origin: Dezhou, Shandong
HS Code: 8544492100