Before the gearless Motor is officially operated, a system zero position is recognized by the inverter and then stored as a parameter. If the system zero adjustment is not accurate, the inverter will not be able to control the motor well, or even make the motor out of control. Therefore, for Super-Star elevators, the encoder phase should be adjusted after self-learning. Remove the wire rope before positioning the encoder. 1. Go to the REGULATION PARAM/Test generator/Test gen mode menu and set the parameter Modify Test Gen Mode to 4 Magn curr ref. 2. Enter the REGULATION PARAM/Test generator/Test gen cfg menu and set the parameters. Gen hi ref 5000 Gen low ref 5000 The set values ​​of these two parameters must be such that the output current of the inverter after ENABLE is close to or the rated current of the motor < can be monitored through the MONITOR menu>. 3.Enable the inverter. The motor will run and stop at a fixed position. At this point, the phase adjustment can be done by mechanical (A) or software (B). *Mechanical positioning (I recommend mechanical positioning if this is possible). 4. View the value of the variable sin-Cos Res pos in SERVICE/Brushless. 5. Loosen the parts of the fixed encoder and carefully rotate the angle of the encoder until sin-Cos Res pos=0. 6. Fix the encoder at this time, the phase adjustment has been completed. 7.Disable the inverter, reset the parameter Test gen mode in the menu REGULATION PARAM/Test generator to 0 off. 8. Save the parameters. *Software positioning 4. Repeat. Disable the drive several times until the motor no longer moves. 5. Write the value of the variable Int calc offset in the menu SERVICE/Brushless directly to the variable sin-Cos Res off. 6.Disable the inverter, reset the parameter Test gen mode in the menu REGULATION PARAM/Test generator to 0 off. 7. Save the parameters. Motor Hydraulic Oil Pump Motor,Water Pump Motor,Voltage Induction Motor,High Tension Motor Shaoxing AnFu Energy Equipment Co.Ltd , https://www.sxanfu.com